Standard: | GB/T9330.3-2008 |
Brand: | FenJiang / Asian Port |
Model: | KYJV |
Conductor Material: | OFC(copper content:99.99%) |
Cores Number: | Multi-core |
Insulator Material: | XLPE |
Nominal Voltage: | 450/750V |
Colors: | Red Yellow Blue Green Black |
Application
Cables Features
In addition, cross-linked polyethylene insulated control cable also has the following 8 major advantages:
Conditions of Use:
XLPE insulated control cable, has several models, different models of the cable has different name and application — —
XLPE insulated control cables | ||
model | name | application |
KYJV | XLPE insulated PVC sheathed control cable | For laying indoors, cable trench, pipeline and other fixed places |
KYJYP | XLPE insulated PVC sheathed control cable braided shield | For laying indoors, cable trench, pipeline and other requirements on shielding |
KYJVP2 | XLPE insulated PVC sheathed copper shielded control cable | For laying indoors, cable trench, pipeline and other requirements on shielding |
KYJVP3 | XLPE insulated PVC sheathed aluminum composite tape shield control cable | For laying indoors, cable trench, pipeline and other requirements on shielding |
KYJV22 | XLPE insulated PVC sheathed control cable | For laying indoors, cable trench, pipeline, direct burial withstand greater mechanical force fixed installation |
KYJVP2-22 | XLPE insulated PVC sheathed copper tape shield steel tape armored control cable | For laying indoors, cable trench, pipeline, direct burial withstand greater mechanical force fixed installation |
KYJV32 | XLPE insulated PVC sheathed steel wire armored control cable | Suitable for water or high drop area, can bear external mechanical forces and considerable tension |
KYJVR | XLPE insulated PVC sheathed control cable | For laying indoors, movable and flexible |
KYJVRP | XLPE insulated PVC sheathed control cable braided shield | For laying indoors, movable and flexible shield occasions |
NOTE: This series’ core of cable is recommended for: 2、3、4、5、7、8、10、12、14、16、19、24、27、30、37、44、48、52、61. |
Different types of cross-linked polyethylene insulated control cable, which conductor interface and core number are in different — —
model | Nominal cross section/mm² | ||||||
0.75 | 1.0 | 1.5 | 2.5 | 4 | 6 | 10 | |
Cores Number | |||||||
KYJV、KYJVP KYJYP、KYJYP | 2~61 | 2~14 | 2~10 | ||||
KYJVP2、KYJVP3 KYJYP2、KYJYP3 | 4~61 | 4~14 | 4~10 | ||||
KYJV22、KYJV23 | 7~61 | 4~61 | 4~14 | 4~10 | |||
KYJVP2-22、KYJVP2-23 | 7~61 | 4~61 | 4~14 | 4~10 | |||
KYJV32、KYJV33 | 19~61 | 7~61 | 4~14 | 4~10 | |||
Note:Cable specifications not listed in this table may be increased according to require |
LPE insulated cable control chart — —
1. Conductor2.Insulator3. Tape4. Braided shield5. Steel shield6. Inner sheath7. Steel tape armor8. Steel wire armored9. Outer Sheath
LPE insulated cable control parameters — —
Finished cable conductor DC resistance at 20℃:
Project | Unit | Technical Specifications | |||||||
Conductor DC Resistance at 20℃ | Ω/km | Nominal Cross mm² | 0.75 | 1.0 | 1.5 | 2.5 | 4 | 6 | 10 |
A、B class | 24.5 | 18.1 | 12.2 | 7.41 | 4.61 | 3.08 | 1.83 | ||
R class | 26.0 | 19.5 | 13.3 | 7.98 | / | / | / |
The finished cable should withstand 3.0kV / 5min frequency AC voltage test, insulation without breakdown.
Finished cable conductor insulation resistance at 90℃:
project | unit | Technical Specifications | |||||||
Insulation resistance at 90℃ | MΩ.km | Nominal Cross mm²; | 0.75 | 1.0 | 1.5 | 2.5 | 4 | 6 | 10 |
A class | 1.20 | 1.10 | 1.10 | 1.0 | 0.85 | 0.70 | / | ||
B class | 1.4 | 1.30 | 1.0 | 0.90 | 0.77 | 0.65 | 0.65 |
XLPE insulated control cables heat resistance, cold resistance, chemical resistance, insulation resistance and service life is far superior than PVC.
Contact