sign: Horn antenna with small beam angle.
Should be used: liquid measurement or short-range solid measurement. Can adapt to the environment with complex process conditions.
Maximum range: 30m
Measurement accuracy: ±10mm
Process connection: flange 316L
Antenna material: stainless steel 316L/PTFE
Process temperature: -40…200°C
Process pressure: -1.0…40bar
Frequency range: 6GHz
Signal output: Two-wire system/four-wire system 4…20mA/HART
Detailed introduction:
GDRD53
Permit
P Standard type (non-explosion-proof)
I Intrinsically safe type (Exia IIC T6) (only aluminum housing is available)
C Intrinsically safe type + marine license (Exia IIC T6) (only stainless steel shell is available)
G Intrinsically safe type + flameproof type (Exd [ia]ia IIC T6) (see "Note" below for optional housing)
Antenna type/material
C Horn antenna 50/stainless steel 316L (only for waveguide installation)*
D Horn antenna 80/stainless steel 316L (only for waveguide installation)*
E Horn antenna 100/Stainless steel 316L
F Horn antenna 150/Stainless steel 316L
G Horn antenna 200/Stainless steel 316L
Antenna extension tube
A None
B 200mm
C 500mm
D 1000mm
E 2000mm
X Special customization
Process connection
FA flange DN50 PN1.6 stainless steel 316L (GB/T9119-2000)
FB flange DN80 PN1.6 stainless steel 316L (GB/T9119-2000)
FC flange DN100 PN1.6 stainless steel 316L (GB/T9119-2000)
FD flange DN150 PN1.6 stainless steel 316L (GB/T9119-2000)
FE flange DN200 PN1.6 stainless steel 316L (GB/T9119-2000)
YP Special
Sealing/process temperature
2 Viton/-40~+130℃
3 Kalrez/-20~+130℃
4 Viton/-40~+200℃with heat sink (selected when the process temperature is greater than 100℃)
5 Kalrez/-20~+200℃with heat sink (selected when the process temperature is greater than 100℃)
Electronic components
B (4~20)mA/HART two-wire system
C (4~20)mA/(22.8~26.4)V DC/HART two-wire/four-wire system
D (198~242)V AC/HART four-wire system
Enclosure rating
A Aluminum/IP67
B Plastic/IP66
D Aluminum two-chamber/IP67
G Stainless steel 316L/IP67
Cable entry
M M20x1.5
N ½NPT
On-site display/programming
A belt
X without
Purge
A belt
X without
Note: Intrinsically safe + marine license (Exia IIC T6) is limited to "A" or "B" electronic components and "G" type enclosure; intrinsically safe + flameproof type (Exd [ia]ia IIC T6) is limited to use "D" shell.
Contact
Supplier